FGD4 SAFE AREA GAS DETECTOR

FGD4 SAFE AREA GAS DETECTOR

Versions available for the detection of:

  • Carbon Dioxide - using temperature-compensated infrared sensors.
  • Oxygen or Toxic Gases – using electrochemical sensors.

Features:

  • Competitively priced
  • Wide power supply range of 8 to 24 volts dc
  • Compact and lightweight
  • Industry standard 4 to 20 mA output
  • Optional weather guard
  • Plug-in replaceable gas sensors

Description:

The FGD4 series gas detectors are powered from an 8 to 24 volts dc power supply using the industry standard 4 to 20mA two-wire current loop to transmit the gas level to a separate control panel such as the Status Scientific Controls LC Series. * The Carbon Dioxide version uses infrared gas detection technology and requires a third connection to power the infrared sensor.

The detector is a safe area fixed gas detector for the detection of gases such as oxygen, carbon monoxide, carbon dioxide, sulphur dioxide, hydrogen sulphide, chlorine etc.

It comprises an instrument housing with one cable gland entry. The housing contains the connection terminals, electronics and gas sensor which is screwed into the bottom of the housing. The unit may be optionally fitted with a protective weather guard (see above).
Calibration of the FGD4 can be carried out simply by using ZERO and SPAN buttons inside the instrument provided that the concentration of the calibration gas is the same as that used for factory calibration of the detector (refer to the instrument calibration certificate for details).

Alternatively, the purpose designed plug-in hand held configuration unit shown above may be used together with any appropriate test gas concentration.